What size conduit to garage for 100amp service?
What size conduit do I need to run to make it relatively easy to pull 100amp service wiring through? Figuring 2" with two 90 degree sweepers. May not pull the wiring until next year when I redo my garage but have construction crew digging up the yard and wanting to lay the conduit now.
Also heard I can't run other wiring in the same conduit as the service line so probably should run another 1 1/4 line as well for lights and anything else I want to control from the house?
_________________ 1976 Bronco "Green, Yellow, whatever", 1969 Bronco "Red", 1972 Bronco Stocker "Kind of Blue/Grayish"
|
Thu Jul 14, 2016 2:31 pm |
|
|
Eck
Official CCB Member
Joined: Thu Oct 25, 2012 9:33 pm Posts: 2460
|
Re: What size conduit to garage for 100amp service?
I'd suggest running a separate conduit for speaker wires so you can have outdoor speakers with no interference. May as well while you can...
_________________ 69 Wagon, 351W, Explorer EFI & Serpentine, ZF5, 35" tires, 3.5 SL, 2 BL, WARN 8274
|
Thu Jul 14, 2016 2:33 pm |
|
|
Gunnibronco
Official CCB Member
Joined: Mon Jan 03, 2011 6:07 pm Posts: 4074 Location: Gardnerville, NV
|
Re: What size conduit to garage for 100amp service?
I don't know the answer. It has to do with the % of the conduit filled by the line. I did direct burial cable to my garage, no conduit.
_________________ "America is at that awkward stage. It's too late to work within the system, but too early to shoot the bastards." – Claire Wolfe 74-AWB 98", ZF5, Atlas4, TGW HP1060 and HP1014 axles, ARBs, 37's, 3.5" lift-5.5" front coil springs, Tahoe rear springs, EFI 302, h-boost, York OBA, 4x4x2, custom dash & gauges 72 U15- Explorer Sport-Candyapple Red (1 of 141)
|
Thu Jul 14, 2016 2:40 pm |
|
|
landshark
Official CCB Member
Joined: Fri Oct 14, 2011 12:16 am Posts: 3942 Location: Denver, Wash Park Area
|
Re: What size conduit to garage for 100amp service?
_________________ 1976 Bronco "Green, Yellow, whatever", 1969 Bronco "Red", 1972 Bronco Stocker "Kind of Blue/Grayish"
|
Thu Jul 14, 2016 4:21 pm |
|
|
Eck
Official CCB Member
Joined: Thu Oct 25, 2012 9:33 pm Posts: 2460
|
Re: What size conduit to garage for 100amp service?
My buddy had this to say on the conduit for the 100amp.
It depends on the wire size. I suggest an 1-1/4" SCH 40 PVC.
Sent from my iPad using Tapatalk
_________________ 69 Wagon, 351W, Explorer EFI & Serpentine, ZF5, 35" tires, 3.5 SL, 2 BL, WARN 8274
|
Thu Jul 14, 2016 5:13 pm |
|
|
ZOSO
Moderator
Joined: Mon Nov 15, 2010 5:58 pm Posts: 3906 Location: Henderson, Co
|
Re: What size conduit to garage for 100amp service?
Go with 2in. It's overkill but will make pulling the wires in easy. And an 1 1/4 for lighting and such will be more than enough.
_________________ Rob
74 Ranger EFI351w, 4r70w, ARB 5.13 9in, ARB 5.13D44, and a bunch of other goodies. Best of all the family memories.
04 Mustang Cobra, KenneBell 2.2 feeding a lot of boost on E85. Tire shredding machine
New project: 77 Bronco Ranger, body work and more body work.
Very little left of a 72 durango tan explorer sport
|
Thu Jul 14, 2016 8:50 pm |
|
|
TOOLMAN
Official CCB Member
Joined: Mon Feb 14, 2011 10:29 am Posts: 768 Location: The MHC
|
Re: What size conduit to garage for 100amp service?
I just buried the power out to my garage a month ago and the electrician did 1-1/4" because I told him I wanted 220v out there someday. And then I ran an extra 1-1/4" for other stuff: coax, sprinkler wire, whatever...
_________________ Wilma - 71 1/2 Wagon; 3 1/2" WH lift, 1" BL, NP435, Chebby disc front, WH twin stick D20, EFI 302, Cool hood scoop, mucho cancer; purchased in 1990.
|
Fri Jul 15, 2016 7:06 am |
|
|
landshark
Official CCB Member
Joined: Fri Oct 14, 2011 12:16 am Posts: 3942 Location: Denver, Wash Park Area
|
Re: What size conduit to garage for 100amp service?
Cool thx for all the info. Iam going with 2" for service and 1 1/4 for extras
_________________ 1976 Bronco "Green, Yellow, whatever", 1969 Bronco "Red", 1972 Bronco Stocker "Kind of Blue/Grayish"
|
Fri Jul 15, 2016 8:03 am |
|
|
|
|